APC - Schneider Electric Galaxy VS GVSUPS100KRHS
UPS - AC 380/400/415 V - 100 kW - 100000 VA - 3-phase - no battery - Ethernet 10/100/1000 - RAL 9003, white gloss - with Start-Up Service 5X8
APC
GVSUPS100KRHS
N/A
0731304418320
N/A
New
Product Description
Additional Details
What's Included
Main Specifications | |
---|---|
Product Description | Schneider Electric Galaxy VS GVSUPS100KRHS - UPS - 100 kW - 100000 VA |
Device Type | UPS - external |
Bundled Services | Start-Up Service 5X8 |
Weight | 639.33 lbs |
Input Wiring | 3-phase |
Input Voltage | AC 380/400/415 V |
Output Voltage | AC 380/400/415 V ± 1% |
Power Capacity | 100 kW / 100000 VA |
Power Redundancy | Yes |
Battery | No battery |
Networking | Ethernet 10/100/1000 |
Remote Management Protocol | Modbus |
Included Accessories | Dust filter |
Color | RAL 9003, white gloss |
Dimensions (WxDxH) | 20.5 in x 33.3 in x 58.5 in |
Manufacturer Warranty | 1-year warranty |
General | |
Device Type | UPS - external |
Bundled Services | Start-Up Service 5X8 |
Color | RAL 9003, white gloss |
Expansion / Connectivity | |
Interfaces | 1 x management (Gigabit Ethernet) |
Manufacturer Warranty | |
Service & Support | Limited warranty - 1 year - on-site |
Miscellaneous | |
Included Accessories | Dust filter |
Features | Audible alarm, Parallel Capability, built-in static bypass, 4.3" touch screen LCD display |
Compliant Standards | IEC 62040-2, FCC Part 15 A, IP21, EN 62040-2, IEC 62040-1, EN 62040-1, UL 1778 5th edition, IEC 60721-4-2 level 2M2 |
Networking | |
Remote Management Interface | Ethernet 10/100/1000 |
Remote Management Protocol | Modbus |
Environmental Parameters | |
Min Operating Temperature | 32 °F |
Max Operating Temperature | 104 °F |
Humidity Range Operating | 0 - 95% (non-condensing) |
Sound Emission | 68 dBA |
Battery | |
Type | No battery |
Power Device | |
UPS Technology | On-line |
Power Redundancy | Yes |
Power Redundancy Scheme | N+1 |
Input Voltage | AC 380/400/415 V |
Input Voltage Range | AC 340 - 460 V |
Frequency Provided | 50/60 Hz ± 0.1% |
Input Voltage Margin | ± 10% |
Input Wiring | 3-phase |
Frequency Required | 40 - 70 Hz |
Output Voltage | AC 380/400/415 V ± 1% - 50/60 Hz |
Power Capacity | 100 kW / 100000 VA |
Output Waveform | Sinewave |
Total Harmonic Distortion (THD) | 3 % |
Dimensions & Weight | |
Width | 20.5 in |
Depth | 33.3 in |
Height | 58.5 in |
Weight | 639.33 lbs |
Dimensions & Weight (Shipping) | |
Shipping Width | 25.2 in |
Shipping Depth | 39 in |
Shipping Height | 66.1 in |